| Sign In | Join Free | My futurenowinc.com |
|
| Categories | Vacuum Circuit Breaker |
|---|---|
| Brand Name: | XG |
| Model Number: | ZN12 |
| Certification: | ISO CCC |
| Place of Origin: | XIAN, China |
| MOQ: | 1 SET |
| Payment Terms: | L/C, T/T, D/A, D/P, Western Union, MoneyGram |
| Supply Ability: | 2000 SET |
| Delivery Time: | 7-15 DAYS |
| Packaging Details: | WOODEN CASE |
| Product Name: | ZN12 11KV Vacuum Circuit Breaker |
| Rated Voltage: | 3.6KV 6.6KV 7.2kV, 12kV, 17.5kV |
| Rated Current: | 400A 630A, 1250A, 1600A, 2000A, 2500A, 3150A, |
| Frequency: | 50hz/60Hz |
| Poles Number: | 3 |
| Phase: | three phase |
| Medium: | vacuum |
| Standard: | GB, IEC Standard |
| Type: | Vacuum Circuit Breaker Indoor |
| Company Info. |
| Xi'an Xigao Electricenergy Group Co., Ltd. |
| Verified Supplier |
| View Contact Details |
| Product List |
ZN12 11KV Vacuum Circuit Breaker Indoor High Voltage 3 Phase
1. ZN12-12 Types Vacuum Circuit Breaker
ZN12 11KV Vacuum Circuit Breaker is suitable for power system with 3-phase AC 50HZ, rated voltage 11KV, it can be used as load current, overload current and fault current for mining enterprises, power plant and substation.
2. ZN12-12 Types Vacuum Circuit Breaker Parameter list
| no. | item | unit | data | ||||
| 1 | 2 | 3 | 4 | 5 | |||
| 1 | rated voltage | kv | 12 | 12 | 12 | 40.5 | 40.5 |
| 2 | rated current | A | 1250 | 1600 | 2000 | 1600 | 2000 |
| 3 | rated short circuit breaking current | KA | 31.5 | 31.5 | 31.5 | 25 | 31.5 |
| 4 | Dynamic and stable current (peak) | KA | 100 | 100 | 100 | 80 | 100 |
| 5 | Thermal stability of 4 s current 50 ka (3 s) | KA | 31.5 | 31.5 | 31.5 | 25 | 25 |
| 6 | The rated short circuit close current (peak value) | KA | 100 | 100 | 100 | 80 | 80 |
| 7 | Rated short circuit breaking current times | TIME | 50 | 30 | |||
3. Applicate of ZN12-12 Types Vacuum Circuit Breaker
No fire, explosion hazard, serious filthy, chemical corrosion, as well as places of intense vibration.
Relative humidity: daily average of not more than 95%, month average of not more than 90%.
Altitude: not exceed 1000m.
Earthquake intensity: not more than ten.
Ambient temperature: not higher than +40 °C, not less than -15°C
4. Photo and drawing
5. Factory

6. Delivery

|