I. Key Functions
1. Synchronization Check – When both sides of the network are
energized, the circuit breaker can only be closed if the voltage
difference (ΔU), frequency difference (Δf), and phase angle
difference (Δφ) all fall within the preset limits.
2. Voltage Check – When one side is energized and the other is not,
this function verifies that the power flow direction is correct and
the dead-time requirement is met, preventing load-side
energization.
3. Dual Circuit Breaker Scenario – With two completely independent
stages (Stage 1/Stage 2) built in, it can monitor the closing
conditions of two circuit breakers simultaneously, suitable for
applications such as dual busbar systems, ring main units, or
generator-transformer unit configurations.
II. Key Parameter Ranges
- Voltage difference ΔU: 2%…40% × Un (1% step)
- Frequency difference Δf: 0.02…0.50 Hz (0.01 Hz step)
- Phase angle difference Δφ: 5°…50° (1° step)
- Slip cycle measurement threshold: >0.15 × Un for calculating
Δf/Δφ
- Deadband time (Voltage-check tVC): 0.1…20 s
- Circuit breaker tripping time compensation tCB: 0…500 ms
- Rated voltage input: 100 V or 110 V (50/60 Hz)
- Auxiliary power supply: 80…265 V AC/DC or 18…80 V DC (Optional
modules: SPFU 240R4 / SPFU 48R4)
III. Hardware and Communication Interface
- 19" 6U rack-mount enclosure, IP54 front panel; Weight ≈ 3 kg
- 8 output relay contacts: 2× heavy-duty (CB closing pulse), 6×
signal (start, trip, device fault)
- Continuous hardware self-test: Internal fault <120 ms triggers
IRF signal and locks output
- Rear fiber optic SPA-BUS serial port (standard), compatible with
ABB LonWorks/SCADA via SPA-ZC21/17 module; supports remote reading
of real-time ΔU, Δf, Δφ values and event logging
IV. Typical Industry Applications
- 6 kV power plant auxiliary busbar switching/tie-breaker
- Hydro power plant generator output circuit breaker (GCB)
synchronization
- 220 kV substation double busbar switching operations
- Oil platform ring main unit (DR) switchgear synchronization
- SPACOM upgrade – SPAU 140 C and SPAU 341 C are directly
interchangeable on the rail; only parameter settings need to be
updated
Product details pictures


Related products
| SPAU 110 C | SPAU 121 C |
| SPAU 140 C | SPAU 130 C |
| SPAU 320 C | SPAU 300 C |
| SPAU 341 C | SPAU 330 C |
| SPAJ 140 C | SPAF 140 C |
| SPAJ 142 C | SPAJ 141 C |
| SPAJ 160 C | SPAJ 144 C |
| SPAC 315 C | SPAM 150 C |
| SPAC 320 C | SPAC 317 C |
| SPAD 346 C | SPAS 120 C |
|