GA700 Series High-Performance Multifunctional Frequency Converter
The GA700 inverter series builds upon Yaskawa's legacy of
high-quality drives, designed around the core principles of
"Versatility", "Ease of Use", and "Reliability". Featuring advanced
motor control for enhanced efficiency and integrated peripheral
devices to reduce system costs, it delivers practical solutions
with excellent global environmental adaptability.
Core Features & Advantages
Control Performance
Open/closed-loop vector control compatible with IM/PM/SynRM motors;
high torque without PG (±5% torque accuracy); max output frequency
up to 590Hz for stable operation and fast response.
Energy Efficiency & System Cost
Automatic energy-saving mode with integrated DC reactor, brake
transistor, and EMC filter to reduce harmonics and minimize
peripheral components.
Ease of Use & Maintenance
Guided startup, multi-language keypad, parameter backup/replication
with DriveWizard Mobile/Desktop support for fast commissioning and
reduced downtime.
Safety & Compliance
STO (SIL CL3, PLe, Cat.3) safety function with 24V auxiliary power
supply for communication maintenance and life prediction
monitoring.
Environmental Adaptability
Operating temperature: -10~60℃ (no derating at 50℃); coated PCB;
optional vibration resistance; multi-protocol communication for
global deployment.
Industry-Specific Functions
Specialized features for winding/wire drawing including tension
control, roll diameter calculation, taper adjustment, and thread
breakage detection.
Key Specifications
| Parameter | Specifications/Ranges |
|---|
| Voltage Class | 200V class, 400V class (3-phase) |
| Power Range | 200V class: 0.4–110kW; 400V class: 0.4–355kW (ND/HD variants) |
| Overload Capacity | ND: 110% for 60s; HD: 150% for 60s |
| Control Modes | V/f, Open-loop Vector, Closed-loop Vector, Torque Control |
| Maximum Output Frequency | Up to 590Hz |
| Safety Function | STO (SIL CL3, PLe, Cat.3) |
| Integrated Components | DC reactor (30kW ND and above), brake transistor (≤90kW ND), EMC
filter |
| Operating Temperature | -10~60℃ (no derating at 50℃) |
| Communication Protocols | Standard: Modbus RTU; Optional: EtherNet/IP, Profinet, EtherCAT |
| Protection Class | Open type: IP20; Optional: IP54 |
Core Model Selection
| Model | Voltage/Phase | Rated Power (ND) | Rated Power (HD) | Core Configuration |
|---|
| GA70C4002BBA | 400V 3φ | 0.55 kW | 0.4 kW | Built-in EMC, STO, Sensorless Vector |
| GA70C4004BBA | 400V 3φ | 1.1 kW | 0.75 kW | Built-in EMC, STO, Sensorless Vector |
| GA70C4008BBA | 400V 3φ | 2.2 kW | 1.5 kW | Built-in EMC, STO, Sensorless Vector |
| GA70C4018BBA | 400V 3φ | 5.5 kW | 4.0 kW | Built-in EMC, STO, Sensorless Vector |
| GA70C4023BBA | 400V 3φ | 7.5 kW | 5.5 kW | Built-in EMC, STO, Sensorless Vector |
Configuration & Selection Guidelines
- Control Modes: V/f, Open-loop/Closed-loop Vector; supports IM/PM/SynRM motors;
sensorless high-torque startup; max output frequency 590Hz
- Integrated Components: Built-in DC reactor (30kW ND and above), brake transistor (≤90kW
ND), EMC filter (common C3 class)
- Safety: STO (SIL CL3, PLe, Cat.3) as standard for safety-critical
applications
- Environment: Operating temperature -10~60℃ (no derating at 50℃); optional
coated PCB and vibration resistance
- Communication: Standard Modbus RTU; optional EtherNet/IP, Profinet, EtherCAT for
system integration
Application Fields
General Industrial Manufacturing
Medium & small machine tool factories, electronics factories,
automotive parts factories leveraging high-precision vector
control, wide temperature range, and multi-motor synchronization
capabilities.
HVAC & Water Treatment
Commercial buildings, municipal water treatment plants, data
centers with automatic energy-saving mode, voltage fluctuation
tolerance, and constant pressure control.
Material Handling & Logistics
Ports/warehouses, e-commerce sorting centers, mines with sensorless
vector control, multi-protocol compatibility, and dust/moisture
resistance.
Textile & Printing
Textile factories, printing plants, non-woven fabric production
with tension control, roll diameter calculation, and high-precision
speed synchronization.
Food & Beverage
Dairy factories, beverage filling plants, canning factories with
optional IP65 stainless steel enclosures, rapid start/stop, and
wide voltage adaptation.
Common Questions & Solutions
Q: The GA700 triggers EMC warnings during testing. What's wrong?
A: Check if your model has the "BBA" suffix (built-in EMC filter).
Ensure proper wiring separation between power and control cables
(≥10cm apart) and verify adequate ground wire thickness and
connection.
Q: Inverter shuts down with "OV" (overvoltage) error in areas with
voltage fluctuations.
A: Adjust "Voltage Fluctuation Tolerance" to 15% in parameters. For
frequent deceleration applications, use built-in brake transistor
with external brake resistor to dissipate regenerative voltage.
Q: Can GA700 work with existing Profinet systems?
A: Yes, select "Profinet option" when ordering. Ensure PLC baud
rate matches (100Mbps) and enable "Profinet Communication" in
parameter Pn001 during commissioning.
Q: Keypad malfunctions in humid environments.
A: Replace standard keypad with optional IP54 waterproof keypad or
install inverter in sealed electrical cabinet with dehumidifier.
Q: Energy savings potential for fan systems?
A: Automatic energy-saving mode adjusts motor speed according to
air pressure, typically saving 25-40% energy compared to
power-frequency operation.