| Brand Name: | COENG | 
| Model Number: | HV500 | 
| Certification: | EC | 
| Place of Origin: | China | 
| MOQ: | 1 | 
| Payment Terms: | L/C, T/T, Western Union | 
| Supply Ability: | 20000sets/year | 
| Delivery Time: | 10-30working days | 
| Packaging Details: | Carton, plywood case | 
| Protection Grade: | IP20 | 
| Cooling Way: | Forced Air Cooling | 
| Efficiency: | 5.5kW~22kW: ≥93%; Above 30kW: ≥95% | 
| Input Voltage: | 200V (-15%) ~240V (+10%) 3Phase , 380V (-15%) ~480V (+10%) 3Phase, 500V (-15%) ~690V (+10%) 3Phase | 
| Input Frequency: | 50Hz/60Hz±5% | 
| Output Voltage: | 0V~Input voltage | 
| Output Frequency: | 0Hz~500Hz | 
| Company Info. | 
| SHENZHEN COENG TECH CO., LTD. | 
| Verified Supplier | 
| View Contact Details | 
| Product List | 
HV500 High Performance VFD Variable Frequency Drive Converter Vector Control Frequency Inverter
Product Description
Based on the superior control performance of the HD2000 engineering VFD, the HV500 is a high-performance VFD with product concepts of “universal”, “easy to use” and “durable” for medium/high-end industrial and single-drive applications.
Product Characteristics
HV500 VFDs Feature


| Optional | Module | Function | 
| Keyboard Base | HVKMB | Depending on the situation, the base can be installed in the
specified position and the drive can be operated by operating the keyboard  | 
| Communication Adapter | HVCOM-USB | The drive can achieve high-speed communication with the computer via this option | 
| Profibus-DP Expand Card | HVCOM-DP | It is for Profibus-DP bus communication, It can fulfill the monitoring and diagnostics of inverters | 
| ABZIncremental Code disk Expansion Card  | HVPG-ABZ | Code disk expansion card, incremental code disk for ABZ signal output, power programmable control, compatible single/bipolar output of the code disk | 
| CANopen Expansion Card | HVCOM-CAN | It is for CANopen bus commnication, it can fulfill the monitoring and diagnostics of inverters | 
| Three-phase voltage detection module  | HVVMU | Detection of three-phase voltage, it can be used for permanent
magnetic synchronous motor soft start grid, speed tracking and other functions  | 
Technical Specification
| Technical Specification | ||
| Input/output Power  | Input Uin | 200V (-15%) ~240V (+10%) 3Phase , 380V (-15%) ~480V (+10%) 3Phase, 500V (-15%) ~690V (+10%) 3Phase  | 
| Input Frequency | 50Hz/60Hz±5% | |
| Unbalance Degree of Uin | ≤3% | |
| Output Uout | 0V~Input Uin | |
| Output Frequency | 0Hz~500Hz | |
| Control Performance  | Motor Type | Asynchronous / Synchronous | 
| Control Method | V/F, OLVC (Open-Loop Vector Control), CLVC (Close-Loop Vector Control) | |
| Range of Speed Regulation | 1:10 V/F, 1:100 OLVC, 1:1000 CLVC | |
| Start Torque | VF: 100% (0.5Hz), OLVC: 150% (0.5Hz), CLVC: 180% (0Hz) | |
| Torque Precision | ≤5%, Vector Control | |
| Torque Pulsation | ≤5%, Vector Control | |
| Speed Regulation Precision | OLVC 0.2%, CLVC 0.01% | |
| Torque Response | ﹤5ms, Vector Control | |
| Dynamic Speed Reduction | OLVC<0.5%*s, CLVC<0.3%*s | |
| Acceleration and Deceleration Time | 0.0s~3200.0s, 0.0min~3200.0min | |
| Torque Lifting | 0.0%~30.0% | |
| Overload | Heavy Load Application 150% 1min/5min, Light Load Application 110% 1min/5min | |
| V/F Curve | Multiple ways: linear V/F curve, 5 kinds of torque reduction characteristic curve mode (2.0 power, 1.8 power, 1.6 power, 1.4 power, 1.2 power), user-defined VF curve | |
| Input Frequency Accuracy | Digital: 0.01Hz, Analog: 0.01Hz | |
| Control Performance  | Acceleration and Deceleration Curve | Straight, S Curve | 
| Multiple Speed-Steps Operation | 16-Speed Steps Operation through control terminals | |
| Automatic VoltageAdjustment (AVR)  | Keeping the output voltage constant automatically when the grid voltage changes within a certain range | |
| Fixed Length | Setted and Fixed Length Control | |
| In-build PID | It Can Easily Constructed Closed loop control system | |
| Enhencement Function | Free Function Block | |
| Input/output Power  | Set Frequency | Keyboaed, UP/DOWN Terminals, Multiple Speed-Steps Operation, Terminals Pulsation, Com | 
| Analog Input Terminals | AI1: 0V~10V/-10V~10V, AI2: 0V~10V/0(4) mA~20mA | |
| Digital Input Terminals | DI1-DI6, 6 programmable digital input terminals, optocoupler isolation, compatible with drain/source input | |
| Digital Input/Output Terminals | DIO1: Fast pulse output, normal input/output; DIO2: fast pulse input, normal input/output | |
| Anolog Output Terminals | 2 Strings 0V~10V/0 (4) mA~20mA | |
| Relay Output | 2Strings Contact Type FormC | |
| Motor Temperature Detection | Support PT100/PT1000/KTY84 | |
| STO Interface | SIL3/PLe Safe torque shutdown function | |
| Com | Com Protocol | Modbus RTU (Standard), Pro ibus, CANopen, pro inet, Devicenet, Ethercat | 
| Environment | Altitude | Without Derating Operation Within 2000m Altitude; 2000m~4000m, Each 100m lifting, Derating 1% (Current) | 
| Operation Temperature | -25℃~+40℃ (40℃~55℃ Derating) | |
| Humidity | 15%~95%, Without Condensation | |
| Vibration | 3M3, IEC60721-3-3 | |
| Storage Temperature | -40℃~+70℃ | |
| Operation Place | Indoor, Without direct sunlight, no flammable, corrosive gases, liquids and conductive particles | |
| Accessory | Encoding card, communication expansion card, voltage detection card | |
| Protection Function | Short circuit, over current, overload, over voltage, under voltage, phase loss, over temperature, external fault, etc. | |
| Efficiency | 5.5kW~22kW: ≥93%; Above 30kW: ≥95% | |
| Installation Method | Cabinet | |
| Protection Degree | IP20 | |
| Cooling | Forced Air Cooling | |
                                 
                             |